Hongrui Li, Jian Chen, Kaoqi Li

Abstract


In order to study the physical and chemical properties of antifreeze for wet system, the freezing point and fire extinguishing tests
of antifreeze for wet system were carried out with different volume fractions of calcium chloride, magnesium chloride, propylene glycol and
ethylene glycol. The experimental results show that the freezing point of 26% calcium chloride solution is lower than -30? . The combination
of calcium chloride and ethylene glycol can reduce their solution concentration, and the freezing point is lower than -30? . The fire extinguishing efficiency of water mist containing 30% calcium chloride is higher than that of pure water. When 50% ethylene glycol is added to the
water mist, the flame will increase. The fire extinguishing effect of water mist containing 24% calcium chloride and ethylene glycol is similar
to that of pure water mist.

Keywords


Antifreeze; A mist of water; Fire control; Freezing point

Full Text:

PDF

Included Database


References


[1] HUO Yan, ZHAO Jianhe.Temperature characteristics near the ceiling of an inclined channel with finite length in case of fire[J].Journal

of Harbin Engineering University, 2015, 36(4):461-466.

[2] HUO Dong-chen, XU Wei-cheng, XIAO Lin, BAI Xue, GUO Chen-yu, WANG Liang. Study on suppression of oil pool fire in confined

space by low pressure water mist with NaCl [J]. Fire Science and Technology, 2019, 38(5):647-649.

[3] HUANG Xiaojia, CHEN Peng, XIE Shuibo, YAO Weijie, WANG Yi, ZHANG Le. Review and development of antifreezing technology

in automatic sprinkler syetem [J]. Water?Wasterwater Engineering, 2021, 47(4):97-104.